P/N 151392 Rev G2
ECN: 12-207
5824 Serial/Parallel Printer
Interface Module Installation
Instructions
The 5824 Serial/Parallel Printer Interface
Module (5824) connects a compatible fire alarm
control panel (FACP) directly to a printer to
print event history. You can also print system
event logs in real time and detector status from
addressable FACPs.
Note: Installation and wiring of this device must be done in
accordance with NFPA 72 and local ordinances.
Specifications
Compatibility
The 5824 is compatible with all Silent Knight
addressable FACPs and with the 5208
conventional FACP.
Mounting
The 5824 comes in a plastic enclosure which
must be mounted inside the annunciator or
accessory cabinet.
To mount the 5824 plastic enclosure into the
appropriate cabinet:
1. Remove the 5824 cover. Use a small screw
driver if necessary.
2. Remove the 5824 circuit board from the base
by pushing outward on the base snap
retaining tabs and lifting the circuit board
out.
Figure 1: 5824 Circuit Board And Plastic Base
3. Mount the plastic base into the appropriate
accessory cabinet.
4. Replace the circuit board in the plastic base.
Note: It may be necessary to connect the wiring to the circuit
board before the board is replaced into the base.
Operating Voltage: 24 VDC
Current (Alarm and Standby): 50 mA
Max Per FACP Addressable FACPs: 8; 5208 FACP: 1
Ambient Temperature: 32°F to 120°F (0°C to 49°C)
Max Wiring Distance from FACP: 6000 ft. (1829 m)
Mounting: Surface
Dimensions: 6”W x 7-3/4”H x 1-7/16”D
(15.2 cm W x 19.7 cm H x 3.7 cm D)
Parallel Port: Ancillary
Serial Port: Primary Fire Signaling